GDTF-400/400 AC RESONANT TEST SYSTEM

 

Test Object and Requirement

 
The system is specially designed for AC withstand voltage test for below items, with below specifications and requirements.
 

Test Object

Specifications

Test Frequency

Test Voltage

Test Time

GIS, circuit breakers,instrument transformers

220kV or below

30-300Hz

≤395kV

1min

Neutral point of Main transformers

220kV/80MVA, capacitance≤0.02μF

45-65Hz

≤160kV

1min

 
 
 
 
 
 
 
 
 
 
 
Technical Data
 
 Rated capacity: 400kVA
 
 Input power supply: Three phase 380V, 50Hz
 
 Rated voltage: 200kV,400kV
 
 Rated current: 2A, 1A
 
 Working Frequency: 30-300Hz
 
 Output waveform: sine wave
 
 Waveform distortion rate: ≤1%
 
 Working time: constant working of 5mins under rated load. Working of 1min, under 1.1 times of rated voltage
 
 Temperature rise: ≤65K after constant working of 5mins under rated load
 
 Quality factor: Q ≥30 (f=45Hz)
 
 Protective function: Over-current, over-voltage and flashover protections for test object.
 
 Accuracy: 1.5% (RMS)