GDHG-103 VT Calibrator

GDHG-103 VT Calibrator is mainly used to calibrate voltage transformer. It should be used together with other equipment such as load box, standard VT etc.

Features

320*240 LCD screen with back light.
Using advanced circuit and DSP technology, to make resistance-capacitance and phase shift circuit more stable.
Friendly interface, easy operation.
Small size, easy to carry and convenient for on-site test.
With RS232 port, convenient to connect with PC.
Measure active component and reactive component of impedance or admittance for VT or CT secondary loop.
Automatically indicate polarity. If the polarity is incorrect, the instrument will be cut off automatically and alarm.

Specifications

Power supply: 220V±5V
Frequency: 50Hz±0.5Hz
Operation Temperature: 5℃-40℃
Relative humidity: <80%(at 25℃)
Altitude: <2500m

Measuring range
Cophase component(%): 0.0001-200.0, resolution: 0.0001
Quadrature component(min): 0.001-700.0, resolution: 0.001
Impedance(Ω): 0.001-20.0, resolution: 0.0001
Admittance(ms): 0.0001-20.0, resolution: 0.0001

Basic error
Cophase component: ΔX=±(X×2%+Y×2%)±Dx
Quadrature component: ΔY=±(X×2%+Y×2%×34.48)±Dy
X,Y-- Display value of instrument
Dx, Dy-- Quantization error
Dx=2, Dy=5

Error of Percent table: 1.5%

Operation range:
Current: (1%-149%)In    (In =5A)
   (5%-149%)In    (In =1A)
Voltage: (5%-149%) Un    (Un =100V, 150V, 100V/)
   (5%-149%)Un    (Un =100V/3)

Working load:
Current: TO/TX <0.12Ω, cosΦ=1
Voltage: a/x <0.25VA (100V)

Polarity instruction
When the current or voltage is at 5% of rated, error is over 180%, it will indicate
polarity status.
Note: If the current is above 10% of rated current/voltage, but there is no polarity
Instruction, it means there is fault, please do not increase current or voltage.
Otherwise, the instrument will burn out.

Ratio instruction
When the current or voltage is above 5% of rated, error is over 30% and less than 180%, it will indicate ratio mistake.

Insulation and withstand voltage instruction:
Terminal TX and Ground terminal () is short circuit
The shell can withstand 1.5kV/1min voltage.

Power consumption: <25VA
Harmonic suppression ratio: >40db
Dimension: 260*350*150mm
Weight: about 6kg.